4

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 1

Product Overview

Selectable Kickstart

(2)

Selectable kickstart provides a power boost at start-up that is user-adjustable from
0 to 90% of locked rotor torque. The additional power helps motors generate
higher torque to overcome the resistive mechanical forces of some applications
when they are started. The selectable kickstart time is user-adjustable from 0.0 to
2.0 seconds.

Figure 2 - Selectable Kickstart

Current Limit Start

(2)

This starting mode provides a true current limit start that is used when limiting
the maximum starting current is necessary. The Current Limit level is
user-adjustable from 50% to 600% of the motor’s full-load ampere rating, and the
current limit time is user-adjustable from 0 to 30 seconds. Once the MV SMC
Flex controller senses that the motor has reached the up-to-speed condition
during the current limit starting mode, the output voltage automatically switches
to full voltage and the bypass contactor is closed.

Figure 3 - Current Limit Start

(2) Kickstart is also available with Current Limit Start, Dual Ramp Start and Linear Acceleration.

Kickstart

100%

Initial

Torque

Start

Time (seconds)

Run

600%

Percent

Full Load

Current

Start

Time (seconds)

50%