Step 2 – alignment of “side- by-side” plenums, Step 2 – alignment of “side-by-side” plenums – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 200

Advertising
background image

190

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Appendix E

ArcShield Plenum Installation Instructions

Figure 90 - Plenum Placement

STEP 2 – Alignment of “Side-
by-Side” Plenums

Plenums mounted side-by-side must be fastened together through the aligning
holes using 5/16-inch supplied hardware (see

Figure 91

).

Figure 91 - Aligning “Side-by-Side” Plenums

Use recommended torque
value for 1/4-20 fasteners

TIP

Use silicone caulking generously to fill any air gaps once the Plenum has been
securely mounted in place.

IMPORTANT

Any unused holes must be filled with thread forming screws. i.e.: “Lifting Lug
holes”.

All Gaps must be sealed and filled with silicone.