Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

115

Troubleshooting

Chapter 9

Table 18 - Fault Display Explanation

Display

Fault Code

Possible Causes

Possible Solutions

Line Loss (with phase indication)

1, 2, 3

• Missing supply phase
• Motor not connected properly
• Improper or missing current or voltage

feedback

• Check for open line (e.g. blown line fuse)
• Check for open load lead
• Check current transformer connections and

module programming

• Check voltage sensing board connections and

module programming

• Check ribbon cable connections between

Interface Board and Control Module

• Check voltage feedback circuits
• Consult factory

Shorted SCR

4, 5 and 6

• Shorted Power Module

• Check for shorted SCR, replace if necessary

(refer to

Power Circuit Troubleshooting on

page 123

)

Open Gate (with phase indication)

7, 8 and 9

• Open gate circuitry
• Loose gate lead

• Perform power supply tests (

Chapter 3

)

• Check gate lead connections to the gate driver

boards and fiber optics

PTC Power Pole

10

• Controller ventilation blocked
• Controller duty cycle exceeded
• Fan failure
• Ambient temperature limit exceeded

• Failed thermistor
• Failed control module
• Failed gate driver board
• Failed fiber optic cable
• Failed interface board

• Check for proper ventilation
• Check application duty cycle
• Replace fan
• Wait for controller to cool or provide external

cooling

• Check connection or replace thermistor
• Replace control module
• Test or replace gate driver board
• Test or replace cable
• Test or replace interface board; check ribbon

cables

Motor PTC

12

• Motor ventilation blocked
• Motor duty cycle exceeded
• PTC open

• Check for proper ventilation
• Check application duty cycle
• Wait for motor to cool or provide external

cooling

• Check resistance of PTC

Open Bypass

13, 14, 15

• Control voltage is low
• Inoperable bypass contactor

• IntelliVAC fault

• Check control voltage power supply
• Check control circuit operation
• Check control plug on contactor
• Check status of IntelliVAC, correct the condition,

reset the module

No load

16, 17, 18, 40

• Loss of load side power wiring
• Loss of feedback

• Check all load side power connections and

motor windings

• Check voltage sensing module

Line Unbalance

19

• Supply unbalance is greater than the user-

programmed value

• The delay time is too short for the application
• Unbalanced feedback

• Check power system and correct if necessary

• Extend the delay time to match the application

requirements

• Check voltage sensing module

Overvoltage

20

• Supply voltage is greater than user-

programmed value

• Check power system and correct if necessary
• Correct the user-programmed value

Undervoltage

21

• Supply voltage is less than user-programmed

value

• The delay time is too short for the application

• Check power system and correct if necessary
• Correct the user-programmed value
• Extend the delay time to match the application

requirements.

Overload

22

• Motor overloaded
• Overload parameters are not matched to the

motor

• Check motor overload condition
• Check programmed values for overload class

and motor FLC