Metering, Metering i/o – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 26

Advertising
background image

16

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 1

Product Overview

Metering

Power monitoring parameters include:

Three-phase current

Three-phase voltage

Power in MW

Power usage in MWh

Power factor

Motor thermal capacity usage

Elapsed time

Motor speed (full speed %, with use of optional tachometer input)

Notes:

1.

Voltage measurement is not available during the braking operation of the
SMB Smart Motor Braking, Accu-Stop, and Slow Speed with Braking
control options.

2.

The elapsed time and MWh values are automatically saved to memory
every 12 hours.

3.

Motor thermal capacity usage is determined by the built-in electronic
thermal overload. An overload fault occurs when this value reaches 100%.

I/O

The SMC Flex has the ability to accept up to two (2) inputs and four (4) outputs
controlled over a network. The two inputs are controlled at terminal 16 (Option
Input #1), and terminal 15 (Option Input #2). For these two inputs, refer
to

Chapter 4

for the parameter settings and refer to

Chapter 8

for the bit

identification. By using these two terminals as inputs, the Stop Input will need to
be programmed to meet the desired stop functionality.

The four (4) outputs are Aux #1, Aux #2, Aux #3 and Aux #4. All auxiliary
contacts are programmable to the function found on

page 83

. If programmed to

Network or Network NC, they can be controlled over a Network. Please see

Table 16 on page 109

which defines the Logic Command Word (Control).

TIP

For MV applications, some of the I/O are assigned to specific functions. Please
refer to

Status Indication on page 18

for additional details.

Advertising