Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

195

Appendix

F

ArcShield Chimney Installation Instructions

The following instructions are provided to ensure the proper installation and
function of chimney supplied with ArcShield enclosures. Refer to

Appendix D

for additional information related to ArcShield chimney before attempting to
follow these instructions.

Recommended Torque
Values

1/4 -20 Thread Fasteners – 7.5 N-m (6 lb-ft)
5/16 -18 Thread Fasteners – 14 N-m (11 lb-ft)

Figure 101 - Chimney Exhaust Label

General Plenum Layout for
ArcShield Line-up

An example of a general chimney assembly configuration is shown in

Figure 102

.

Chimneys of varying widths are mounted directly over the MV enclosures of the
corresponding width.

DANGER

DANGER

ARC FLASH HAZARD

PRESSURE RELIEF EXIT

AREAS TO BE:

- INACCESSIBLE TO PERSONNEL

WHILE EQUIPMENT ENERGIZED.

- FREE OF OBSTRUCTIONS

(REFER TO USER MANUAL).

SEVERE INJURY OR
DEATH MAY RESULT.

HAZARD D’ARC ÉLECTRIQUE

SORTIE DE L’ÉVENT

RÉGION ÊTRE:

- INACCESSIBLE AUX PERSONNEL

PENDANT QUE L’ÉQUIPEMENT

EST SOUS TENSION.

- DÉMUNI D’OBSTRUCTIONS

(RÉFÉRER AU MANUEL)

RISQUE DE BLESSURES
CORPORELLES GRAVES
OU MÊME LA MORT.