Control terminal designations – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 66

Advertising
background image

56

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 2

Installation

Control Terminal
Designations

As shown in

Figure 35

, the SMC Flex controller contains 24 control terminals on

the front of the controller.

Figure 35 - SMC Flex Controller Control Terminals

Note: The OFF state leakage current for a solid-state device connected to an SMC Flex input must be less than 6 mA.

Terminal
Number

Description

Terminal
Number

Description

11

Control Power Input

(1)

(1) RC snubbers are required on inductive loads connected to auxiliary.

23

PTC Input

(2)

12

Control Power Common

(1)

24

PTC Input

(2)

13

Control Enable Input

(2)

(2) Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems with operation, which may

result in false starting and stopping.

25

Tach Input (-)

14

Control Module Ground

26

Tach Input (+)

15

Option Input #2

(1)(2)

27

Ground Fault Transformer Input

(2)

16

Option Input #1

(1)(2)

28

Ground Fault Transformer Input

(2)

17

Start Input

(1)(2)

29

Aux. Contact #2

(1)

18

Stop Input

(1)(2)

30

Aux. Contact #2

(1)

19

Aux. Contact #1 (Ext. Bypass)

(1)(3)

(3) Aux. Contact #1 is always programmed for Ext. Bypass (NO) to control the bypass contactor in MV applications.

31

Aux. Contact #3

(1)

20

Aux. Contact #1 (Ext. Bypass)

(1)(3)

32

Aux. Contact #3

(1)

21

Not Used

33

Aux. Contact #4 (Normal)

(1)(4)

(4) Aux Contact #4 is always programmed for “Normal” (NO) to control the isolation contactor in MV applications.

22

Not Used

34

Aux. Contact #4 (Normal)

(1)(4)