Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

83

Programming

Chapter 4

Parameter

Option

Kickstart Time
A boost current is provided to the motor for the
programmed time period.

0.0 to 2.0 s

Kickstart Level
Adjust the amount of current applied to the motor during
kickstart.

0 to 90% of locked rotor torque

Stop Input
Allows the user to select the operation of terminal 18,
Stop Input.

Coast, Stop Option

Option 1 Input
Allows the user to select the operation of terminal 16,
Option Input #1.

Disable, Stop Option, Fault, Fault NC, Network

Option 2 Input
Allows the user to select the operation of terminal 15,
Option Input #2.

Disable, Preset Slow Speed, Dual Ramp, Fault, Fault NC,
Network, Clear Fault, Emergency Run

(3)

(3) When programmed for ‘Emergency Run’ and the Option 2 input is energized, a ‘Start’ command will first close the bypass contactor,

then the line contactor for an across-the-line start of the motor. A ‘Stop’ command will open the line contactor first and allow the
motor to coast, regardless of the programmed ‘Stop Mode’. For Pump Option modules, the Option 2 input defaults to ‘Emergency
Run’ for MV applications.

Stop Mode
Allows the user to program the SMC Flex controller for the
type of stopping that best fits the application.

Soft Stop, Linear Speed

Stop Time
This sets the time period which the controller will ramp
the voltage during a stopping maneuver.

0.0 to 120 s

CT Ratio
Scales the CT input to actual motor current (5 amp
secondary assumed). Example: CT Ratio = 150:5,
program 150

1 to 1500

Aux1 Config

(1)

(2)

Contact is provided as standard with the SMC Flex
controller. This contact is located at terminals 19 and 20.
Aux Contacts 1 allows the user to configure the operation
of the contacts.

(1) Not accessible in MV applications for Firmware up to 5.001.
(2) Refer to

I/O on page 16 of Chapter 1

and

Note: on page 18 of Chapter 1

for MV specific functionality.

Normal, Normal NC, Up-to-Speed, Up-to-Speed NC, Fault,
Fault NC, Alarm, Alarm NC, Network, Network NC, External
Bypass

Aux2 Config
Contact is provided as standard with the SMC Flex
controller. The contact is located at terminals 29 and 30.
Aux. Contacts 2 allows the user to configure the operation
of the contacts.

Normal, Normal NC, Up-to-Speed, Up-to-Speed NC, Fault,
Fault NC, Alarm, Alarm NC, Network, Network NC, External
Bypass

Aux3 Config
Contact is provided as standard with the SMC Flex
controller. The contact is located at terminals 31 and 32.
Aux. Contacts 3 allows the user to configure the operation
of the contacts.

Normal, Normal NC, Up-to-Speed, Up-to-Speed NC, Fault,
Fault NC, Alarm, Alarm NC, Network, Network NC, External
Bypass

Aux4 Config

(2)

Contact is provided as standard with the SMC Flex
controller. The contact is located at terminals 33 and 34.
Aux. Contacts 4 allows the user to configure the operation
of the contacts.

Normal, Normal NC, Up-to-Speed, Up-to-Speed NC, Fault,
Fault NC, Alarm, Alarm NC, Network, Network NC, External
Bypass

Parameter Mgmt
Recall of factory default parameter values.

Ready, Load Default