160

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Appendix B

Parameter Information

Group

Parameter Description

Parameter
Number

Units

Min / Max

Default
Settings

User
Settings

Basic Set Up

Stop Mode

(1)

32

Soft Stop
Linear Speed
SMB

(2)

Accu-Stop

(2)

Soft Stop

Stop Time

33

SEC

0…120

0

Basic Set Up/Accu-Stop

Braking Current

35

% FLC

0…400

0

Preset SS/Accu-Stop

Slow Speed Sel

39

SS Low
SS High

SS High

Slow Speed Dir

40

SS FWD
SS REV

SS FWD

Slow Speed Cur

41

% FLC

0…450

0

Slow Running Cur

42

% FLC

0…450

0

Accu-Stop

Stopping Current

43

% FLC

0…400

0

Basic Set Up / Overload

Overload Class

44

Disable
Class 10
Class 15
Class 20
Class 30

Class 10

Service Factor

45

0.01…1.99

1.15

Motor FLC

46

A

1.0…1000.0

1.0

Overload Reset

47

Manual

Manual

Overload

Overload A Lvl

50

% MTU

0…100

0

Underload

Underload F Lvl

51

% FLC

0…99

0

Underload F Dly

52

SEC

0…99

0

Underload A Lvl

53

% FLC

0…99

0

Underload A Dly

54

SEC

0…99

0

Undervoltage

Undervolt F Lvl

55

% V

0…99

80

(3)

Undervolt F Dly

56

SEC

0…99

1

Undervolt A Lvl

57

% V

0…99

0

Undervolt A Dly

58

SEC

0…99

0

Overvoltage

Overvolt F Lvl

59

% V

0…199

0

Overvolt F Dly

60

SEC

0…99

0

Overvolt A Lvl

61

% V

0…199

0

Overvolt A Dly

62

SEC

0…99

0

Unbalance

Unbalance F Lvl

63

%

0…25

0

Unbalance F Dly

64

SEC

0…99

0

Unbalance A Lvl

65

%

0…25

0

Unbalance A Dly

66

SEC

0…99

0

Jam

Jam F Lvl

67

% FLC

0…1000

0

Jam F Dly

68

SEC

0…99

0

Jam A Lvl

69

% FLC

0…1000

0

Jam A Dly

70

SEC

0…99

0

Stall

Stall Delay

71

SEC

0.0…10.0

0

(1) Pump option modules default to “Pump Stop”.
(2) Brake module only.
(3) Do not set below 70.