Plenum exhaust considerations – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 191

Advertising
background image

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

181

ArcShield Unit Information

Appendix D

Figure 80 - Cross-section of plenum extension, dimensions in mm [inches]

Plenum Exhaust
Considerations

The following options for locating the plenum exhaust are presented:

1.

Plenum ducted to an area of the control room where arc gases are
permitted to escape, with plenum extensions (see

Figure 81

,

Figure 82

and

Figure 83

).

2.

Plenum duct to outside of control room (see

Figure 81

and

Figure 82

).

Plan the location where the plenum will exhaust. Ensure that:

There is no access to personnel while equipment is energized.

Area is free of flammable material or vapors

Ensure that adequate space is provided around the plenum exhaust, as outlined in

Figure 81

through

Figure 83

.

633 [25]

584 [23]

IMPORTANT

Be aware that equipment in the area of the plenum exhaust point will be
damaged or destroyed.