Operating in SVĆSuperset Mode

6

6Ć24

The VME master processor writes 21 (hex) to the command byte. There
are no input parameters from the VME master processor. The scanner
writes these parameters to the selected channel’s general data area:

Byte

offset:

Parameter: Description:

021F

scan list length
READ ONLY

The scan list length indicates the number of entries in the scan

list. The scan list length is an 8Ćbit quantity that the scanner

writes to the length of data byte in the control/status area. You

can enter a scan list length of 0.

0220

I/O adapter status word block
READ ONLY

This word block contains four 16Ćbit entries (4 words) for each

adapter - 16 bits for each starting group per adapter (maximum

of 16 groups of entries). See Figure 6.10 and Figure 6.11.

02A0

scan list
READ ONLY

This list is a maximum of 64 bytes long (1 byte per adapter)),

but it contains only 32 distinct physical adapter addresses.. The

list contains one byteĆsized entry for each adapter in the scan

list. An adapter can appear in the list multiple times.

See Figure 6.12 on page 6Ć26.

parameters