Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 47

Advertising
background image

Chapter

Communicating with Remote I/O

4

4Ć10

Figure 4.6

BlockĆtransfer sequence - sending a request

VME

master

processor

The VME master processor sends a

BT WRITE request to scanner

BT#n

The scanner copies the request parameters and data

into its internal queue. In SVĆcompatible mode, the

scanner can queue as many as 42 blockĆtransfer

requests; in SVĆsuperset mode, the scanner can queue

only one blockĆtransfer request.

scanner

queue

BT#a

BT#b

BT#n

During the adapter scan, the scanner polls each adapter in the scan

list. If a blockĆtransfer is pending for that adapter, the scanner sends a

blockĆtransfer request to the adapter. The scanner doesn't receive or

send the block data until the next scan. The scanner transmits only

one blockĆtransfer request per adapter per scan.

1771 I/O

chassis

adapter

#n

input

modules

output

modules

scanner

BT#n

scan n

The scanner writes a

result code in the

confirmation status word.

See chapters 5 or 6.

Output Image Table
Input Image Table
Operating Status Word
Confirmation Status Word
Command Word
Address Word
BT Tag Word

Advertising