5ć19, Set mode – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 70

Advertising
background image

Chapter

Operating in SVĆCompatible Mode

5

5Ć19

SET MODE changes the operating mode of the scanner.

not used

Byte offset

(Hex)

102

104

106

-111B

11E

Name

11C

00H returned means the command was

successful. Any other value indicates

an error.

20H is both sent and returned.

Mode

01 = Program

02 = Test

04 = Run

Bit 7 = semaphore

not used

not used

120

channel A

control/status

not used

mode

channel A

general data

not used

122

-FBF

semaphore

command

confirmation

not used

not used

103

105

11D

120

The VME master processor writes 20 (hex) to the command byte. Then
the VME master processor writes this parameter to the selected channel’s
general data area:

Byte

offset:

Parameter:

Description:

120

mode

Write one of these values (hex):
01

Program mode

02

Test mode

04

Run mode

Values 00, 03, and 05-FF are reserved. If you write a reserved value

to this field, the scanner writes an illegal confirmation error (16H) in the

confirmation status byte.

SET MODE

command byte 20

description

parameters

Advertising