Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 24

Advertising
background image

Chapter

Installing the Scanner

2

2Ć5

For example:

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

SW3

SW2

SW1

These switch settings specify:

SVĆcompatible mode

A24 address space

response to both nonĆprivileged and supervisory access

only channel A is active

These switch settings specify VME address 562,000.

Specifying VME addresses
You specify the first digit (for A16) or first 3 digits (for A24) of the
address space; the remaining digits are always 0. The switches are set
from left to right. For example, to set the address space at 562,000 (hex) in
A24 with one channel active, set the bits as:

A23

A22

A21

A20

A19

A18

A17

A16

A15

A14

A13

A12

0

1

0

1

0

1

1

0

0

0

1

0

(on)

(off)

(on)

(off)

(on)

(off)

(off)

(on)

(on)

(on)

(off)

(on)

Switch

Setting

5

6

2

The last three digits in 562,000 (hex) address are already determined

by the scanner, so there are no switches to set.

VME address space of 562,000 (hex)

A24 address mode with 1 channel active