Chapter

Installing the Scanner

2

2Ć9

Table 2.D

Terminating the remote I/O link

use this

the maximum number of

If your remote I/O link:

use this

resistor

rating:

physical devices that you

can connect on the link is:

racks that you can

scan on the link is:

operates at 230.4 K bit/s
operates at 57.6 or 115.2 K bit/s, and no devices listed below are linked

Scanners 1771ĆSN; 1772ĆSD, ĆSD2;

1775ĆSR, ĆS4A, ĆS4B;

6008ĆSQH1, ĆSQH2

Adapters 1771ĆAS; 1771ĆASB (series A only); 1771ĆDCM
Miscellaneous 1771ĆAF

82W

32

16

connects to any device listed below:

Scanners 1771ĆSN; 1772ĆSD, ĆSD2;

1775ĆSR, ĆS4A, ĆS4B;

6008ĆSQH1, ĆSQH2

Adapters 1771ĆAS; 1771ĆASB (series A only); 1771ĆDCM
Miscellaneous 1771ĆAF

150W

16

16

operates at 57.6 or 115.2 K bit/s, and you do not require over 16 physical devices

You can connect a remote I/O link in one of two ways:

trunkline/dropline—from the drop line to the connector screw terminals

on the remote I/O connectors of the scanner

daisy chain—to the connector screw terminals on the remote I/O

connectors of the scanner and then to the remote I/O connector screw
terminals of the next remote I/O device

Important

: The cable connections for the 6008-SV1R and 6008-SV2R

scanner are opposite from those for the earlier 6008-SV scanner. Make
sure you follow the instructions in Figure 2.1 below.