Byte

offset:

Parameter: Description:

107

module address

The module address is the address of the I/O modules that is to

receive the block data.
The module address is the address of the I/O module that is to

receive the block data. It contains the rack (0-15), group (0-7),

and slot (0 or 1) numbers of the I/O module. See Figure 5.14.

109

blockĆtransfer tag number

The blockĆtransfer tag number is an 8Ćbit integer that uniquely

identifies each blockĆtransfer. The scanner writes a value 0-41 to

the blockĆtransfer request tag number in the control/status area.
Values greater than 41 are reserved. If you write a reserved value

to this field, the scanner writes an illegal confirmation error (16) in

the confirmation status byte.
This tag is returned with the status when the block transfer is

complete so the VME master processor can match the block

transfer status with the request.

11F

length of data

The length of data byte is an 8Ćbit value that specifies the number

of 16Ćbit words (0-64 decimal) to be written to the target

I/O module.
Use the value 0 to let the I/O module determine how many words

the scanner can write. When the blockĆtransfer completes, the 0 is

replaced by the actual number of words written.
Values greater than 64 are reserved. If you write a reserved value

to this field, the scanner writes an illegal confirmation error (16) in

the confirmation status byte.

120

BT data

The BT data is the set of data words (0-64) sent to the target I/O

module. The BT data block ends at offset (length of data - 1).

Figure 5.14

Structure of the address byte

0 = terminals 00-07

1 = terminals 10-17

6

5

4

3

2

1

0

7

Your code for the BT WRITE command should included these tasks:

1. get the semaphore
2. set up the control status area
3. send the command interrupt
4. wait for the result

(either poll for confirmation status or wait for an interrupt)

5. clear the semaphore

coding sequence