Chapter

Operating in SVĆSuperset Mode

6

6Ć4

Table 6.A

Descriptions of the global memory areas

This area: stores the:
input and output image table

input and output data for as many as 16 logical I/O racks with no more than 32 adapters.

control/status area

operating status byte

reflects the current status of the scanner
lets the VME master processor poll the scanner's status without interrupting

ongoing operations
see Figure 6.2 on page 6Ć5

confirmation status

byte

contains the result of the executed command
A result of 00 (hex) indicates the command completed successfully. See chapter 9

for a list of error codes.

command byte

identifies the command the VME master processor wants the scanner to

execute next

address byte

contains I/O rack, group, and slot parameters for block transfer commands
For more information, see

BT READ command on page 6Ć28

BT WRITE command on page 6Ć32

CONTINUOUS BT READ command on page 6Ć36

CONTINUOUS BT WRITE command on page 6Ć40

block transfer tag byte provided by the VME master processor to uniquely identify each oneĆshot block

transfer request or continuous blockĆtransfer entry

block transfer interrupt

byte

indicates the VME interrupt level and interrupt acknowledgement vector for when a

continuous block transfer periodically completes
For more information, see BT WRITE command on page 6Ć32 or BT READ

command on page 6Ć36. Use the SETUP command to specify the interrupt level and

interrupt vector.

input image table

monitor index word

when the input image table monitor is enabled, this word contains the index of the

last entry that changed in the input image table
when the input image table monitor is disabled, this word is undefined
Use the SETUP command to enable or disable the input image table monitor.

semaphore byte

provides for the integrity of command requests, command responses, and completed

oneĆshot block transfers
If bit 7 is set, a VME master processor is using the control/status and general data

area or the scanner just completed a block transfer and set the semaphore so no

other VME master processor will overwrite the data. If the semaphore is set because

of a block transfer, the appropriate VME master will know to come and retrieve the

data and reset the semaphore. If the semaphore bit is clear, the general data area is

available for access by any VME master processor.
Important: A VME master processor doesn't use the semaphore when it accesses

the I/O image table. The VME master processor can access the I/O image

table anytime.
For command requests, the scanner returns status, either confirmation or error, when

the command is complete. When the VME master processor receives the

confirmation status, it must retrieve the data from the general data area and clear the

semaphore.
Important: Only 1 command can be issued at a time. A status confirmation or error

must be received before a new command is issued.