6ć36, Continuous bt read – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 117
Advertising

Chapter
Operating in SVĆSuperset Mode
6
6Ć36
CONTINUOUS BT READ transfers a block of data from the specified
adapter to the scanner’s general data area at regular intervals. When one
block-transfer read completes, the scanner queues another one. The cycle
continues until you disable the continuous block transfer.
The scanner must be in Program mode to execute this command. If the
scanner isn’t in Program mode, the scanner returns error code 13H
(Program mode required) to the confirmation status byte. Once the
command is running, you can halt a continuous block-transfer by switching
the scanner to Program mode.
CONTINUOUS BT READ
command byte 06
description
Advertising