6ć36, Continuous bt read – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 117

Advertising
background image

Chapter

Operating in SVĆSuperset Mode

6

6Ć36

CONTINUOUS BT READ transfers a block of data from the specified
adapter to the scanner’s general data area at regular intervals. When one
block-transfer read completes, the scanner queues another one. The cycle
continues until you disable the continuous block transfer.

The scanner must be in Program mode to execute this command. If the
scanner isn’t in Program mode, the scanner returns error code 13H
(Program mode required) to the confirmation status byte. Once the
command is running, you can halt a continuous block-transfer by switching
the scanner to Program mode.

CONTINUOUS BT READ

command byte 06

description

Advertising