6ć34 – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 115

Advertising
background image

Chapter

Operating in SVĆSuperset Mode

6

6Ć34

The VME master processor writes 02 (hex) to the command byte. Then
the VME master processor writes these parameters to the selected
channel’s control status area:

Byte

offset:

Parameter: Description:

0207

module address

The module address is the address of the I/O module that is to

receive the block data. It contains the rack (0-15), group (0-7),

and slot (0 or 1) numbers of the I/O module. See Figure 6.14.

0209

blockĆtransfer tag number

The blockĆtransfer tag number is an 8Ćbit integer that uniquely

identifies each blockĆtransfer. The scanner writes a value of 0 or 1

to the blockĆtransfer request tag number in the control/status area.
Values greater than 1 are reserved. If you write a reserved value

to this field, the scanner writes an illegal confirmation error (16H) in

the confirmation status byte.
This tag is returned with the status when the block transfer is

complete so the VME master processor can match the block

transfer status with the request.

021F

length of data block

The length of data byte is an 8Ćbit value that specifies the number

of 16Ćbit words (0-64 decimal) to be written to the target

I/O module.
Use the value 0 to let the I/O module determine how many words

the scanner can write. When the blockĆtransfer completes, the 0 is

replaced by the actual number of words written.
Values greater than 64 are reserved. If you write a reserved value

to this field, the scanner writes an illegal confirmation error (16H) in

the confirmation status byte.

0220

BT data

The BT data is the set of data words (0-64) sent to the target I/O

module. The BT data block ends at offset (length of data - 1).

Figure 6.14

Format for the address byte

0 = terminals 00-07

1 = terminals 10-17

6

5

4

3

2

1

0

7

parameters

Advertising
This manual is related to the following products: