6ć15, Scan list – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 96

Advertising
background image

Chapter

Operating in SVĆSuperset Mode

6

6Ć15

SCAN LIST replaces the current scan list. The scanner must be in
Program mode. You can issue a SCAN LIST command without first
issuing an AUTOCONFIGURE command.

Byte offset

(Hex)

0202

0204

0206

-021B

021E

Name

021C

00H returned means the command was

successful. Any other value indicates

an error.

11H is both sent and returned.

1 byte per adapter

(you can enter the same adapter

multiple times)
see Figure 6.5

Bit 7 = semaphore

not used

not used

0220

channel A

control/status

scan list

as many as 64 bytes

-025F

not used

channel A

general data

0260

-02FF

not used

number of entries (0-64)

in the scan list

scan list

length

semaphore

command

confirmation

0203

0205

not used

not used

021D

021F

The VME master processor writes 11 (hex) to the command byte. Then
the VME master processor writes these parameters to the selected
channel’s general data area:

Byte

offset:

Parameter: Description:

021F

scan list length

The scan list length indicates the number of entries (0-64) in

the scan list. The scan list length is an 8Ćbit quantity that the

scanner writes to the length of data byte in the control/status

area. You can enter a scan list length of 0.

0220

scan list

This list is a maximum of 64 bytes long (1 byte per entry), but it

can contain only 32 distinct physical adapter addresses. The

list contains one byteĆsized entry for each adapter you want to

place in the list. An adapter can appear in the list multiple

times. See Figure 6.6 and Figure 6.7.

SCAN LIST

command byte 11

description

parameters