Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 107

Advertising
background image

Chapter

Operating in SVĆSuperset Mode

6

6Ć26

Format item:

Description:

Format item:

Description:

in scan list

bit 12

Contains one of these values:
1

adapter is in the current scan list

0

adapter not in current scan list

group faulted

bit 7

Contains one of these values:
1

fault exists in the fault dependent group

associated with the adapter

0

no fault exists in the fault dependent

group associated with the adapter

adapter attached

bit 11

Contains one of these values:
1

adapter resides at this address

0

no adapter resides at this address

line status

bit 6-4

Contains one of these values (hex):
000

adapter is off line

any other

adapter is on line

value

valid configuration

bit 10

Contains one of these values:
1

adapter type, size, and address are valid

0

adapter type, size, and/or address not

valid; adapter is improperly configured

in fault dependent

group

bit 3

Contains one of these values:
1

adapter is in the fault dependent group

identified by the fault dependent group

number (bits 2-0)

0

adapter is not in a fault dependent group

adapter size

bits 9-8

Contains one of these values (hex):
00

1/4 rack addressing

01

1/2 rack addressing

10

3/4 rack addressing

11

full rack addressing

fault dependent

group number

bits 2-0

The value (0-7 binary) identifies the fault

dependent group to which this adapter belongs.

Figure 6.12

Format for one entry in the scan list

6

5

4

3

2

1

0

7

Format item:

Description:

rack number

bits 5-2

The value (0-15 binary) identifies the rack number.

starting I/O group number

bits 1-0

One of the following values identifies the starting I/O group:
00

group 0

01

group 2

10

group 4

11

group 6

Advertising