5ć13, Scan list – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 64

Advertising
background image

Chapter

Operating in SVĆCompatible Mode

5

5Ć13

SCAN LIST replaces the current scan list. The scanner must be in
Program mode. You can issue a SCAN LIST command without first
issuing an AUTOCONFIGURE command.

not used

not used

scan list

length

Byte offset

(Hex)

102

104

106

-11B

11E

Name

11C

00H returned means the command was

successful. Any other value indicates

an error.

11H is both sent and returned.

1 byte per adapter

(you can enter the same adapter

multiple times)
see Figure 6.5

Bit 7 = semaphore

not used

semaphore

120

channel A

control/status

scan list

as many as 64 bytes

-15F

channel A

general data

160

-FBF

not used

number of entries (0-64)

in the scan list

command

confirmation

not used

not used

103

105

11D

11F

The VME master processor writes 11 (hex) to the command byte. Then
the VME master processor writes these parameters to the selected
channel’s general data area:

Byte

offset:

Parameter: Description:

11F

scan list length

The scan list length indicates the number of entries (0-64) in

the scan list. The scan list length is an 8Ćbit quantity that the

scanner writes to the length of data byte in the control/status

area. You can enter a scan list length of 0.

120

scan list

This list is a maximum of 64 bytes long (1 byte per adapter),

but it can contain only 16 distinct physical adapter addresses.

The list contains one byteĆsized entry for each adapter you

want to place in the list. An adapter can appear in the list

multiple times. See Figure 5.6 and Figure 5.7.

SCAN LIST

command byte 11

description

parameters