Communicating with Remote I/O

4

4Ć3

The scanner keeps a list of all of the devices connected to each channel.
Figure 4.2 shows an example scan list for one channel.

Figure 4.2

Example scan list

SV2R

Rack 1

Rack 2

Rack 3

Ch A

Ch B

Ch B Scan List

Rack

Address

Starting

Group

Rack

Size

Range

1

2

3

0

0

0

Full

1/2

Full

010Ć017

020Ć023

030Ć037

In this example, channel B continually scans the three racks in its scan list.

The steps for setting up a remote I/O system are:

Step: See:
1. configure the remote I/O adapter devices

the device's user manual

2. layout and connect the remote I/O link cable

page 4Ć3 for design

your adapter's installation information

3. specify a scan list

page 4Ć5

Designing a remote I/O link requires applying:

remote I/O link design guidelines
cable design guidelines

Link Design Guidelines

Keep these rules in mind as you design remote I/O links:

All devices connected to a remote I/O link must communicate using the

same communication rate. The rate you choose depends on the VME
operating mode:

This VME operating mode: supports these

communication rate:

SV compatible

57.6 kbps
115.2 kbps

SV superset

57.6 kbps
115.2 kbps
230.4 kbps

Designing a Remote I/O Link