Make remote I/O connections

To connect the remote I/O cable, do the following:

1. Run the cable (1770ĆCD) from the processor to each

remote I/O adapter in the remote I/O system.

2. Connect the signal conductor with blue insulation to the

3Ćpin connector terminal labeled 1 on the scanner and to

each remote I/O adapter in the remote I/O system.

3. Connect the signal conductor with clear insulation to the

3Ćpin connector terminal labeled 2.

4. Connect the shield drain wire to the middle 3Ćpin

terminal (it is not labeled).

5. Tie wrap the remote I/O network cable to the chassis to

relieve strain on the cable.

6. Terminate the remote I/O link by connecting an external

terminator resistor between the remote I/O terminals

labeled 1 and 2.

To another remote I/O device

Clear

Shield

Blue

82Ć

or

150Ć

resistor

Last device on the remote I/O link.

Terminate both ends of a remote I/O link.

1770ĆCD

(Belden 9463)