Addressing I/O

3

3Ć5

32Ćpoint examples

1Ćslot addressing

(1 I/O chassis slot = 1 I/O group = 1 input image word and 1 output

image word = 16 input bits and 16 output bits.)

0
1
2
3
4
5
6
7

Output Image Table

Word #

0
1
2
3
4
5
6
7

Input Image Table

Word #

scanner memory
Rack x

00

17

bits

00

17

bits

ЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙ

Group 0

Group 1

32Ćpoint output module

32Ćpoint input module

ЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙ

32Ćpoint I/O modules use the entire word

of their group and borrow the entire word

of the next group. See ➀.
Since the module is in group 0 and the

inputs for group 0 and group 1 are used,

you must:

install an output module in group 1, or

leave the slot empty

Group 0

32Ćpoint input module

Since the input image table for group 1 is unavailable because it is

being used by the input module of group 0, installing a 32Ćpoint output

module makes use of output image table of group 0 and 1. See ➁.
You can also install 8Ć or 16Ćpoint output modules. But you cannot

install another input module since all the input image space for groups

0 and 1 is used by the input module of group 0.