5ć16, Fault dependent group – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 67

Advertising
background image

Chapter

Operating in SVĆCompatible Mode

5

5Ć16

FAULT DEPENDENT GROUP associates a set of adapters such that if one
adapter in the group faults, all the other adapters in the group fault, going
to their fail-safe mode of operation. The scanner must be in Program mode
to issue this command. You can specify as many as 8 fault groups.

not used

Byte offset

(Hex)

102

104

106

-11B

11E

Name

11C

00H returned means the command was

successful. Any other value indicates

an error.

12H is both sent and returned.

1 byte per starting group

(4 bytes per adapter)
see Figure 5.8 and Figure 5.9

Bit 7 = semaphore

not used

120

channel A

control/status

faultĆdependentĆgroup blocks

32 bytes

-13F

not used

channel A

general data

140

-FBF

not used

semaphore

command

confirmation

not used

not used

103

105

11D

The VME master processor writes 12 (hex) to the command byte. Then
the VME master processor writes these parameters to the selected
channel’s general data area:

Byte

offset:

Parameter: Description:

120

fault dependent group block

There are 4 configurable bits for each starting group entry.
An adapter must be in the current scan list to be assigned to a

faultĆdependent group. If you specify an adapter that is not in

the scan list, the scanner writes an illegal configuration error

(16H) to the confirmation status byte. See Figure 5.8

and Figure 5.9.

FAULT DEPENDENT GROUP

command byte 12

description

parameters

Advertising
This manual is related to the following products: