Specifying a scan list – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual

Page 42

Advertising
background image

Chapter

Communicating with Remote I/O

4

4Ć5

For proper operation, terminate both ends of a remote I/O link by using
external resistors. Use either a 150

W or 82W terminator.

Table 4.A

Selecting the external resistor

the maximum number of

If your remote I/O link:

use this resistor

rating:

physical devices that

you can connect on

the link is:

racks that you can

scan on the link is:

operates at 230.4 K bit/s
operates at 57.6 or 115.2 K bit/s, and no devices

listed below are linked

Scanners

1771ĆSN; 1772ĆSD, ĆSD2;

1775ĆSR, ĆS4A, ĆS4B;

6008ĆSQH1, ĆSQH2

Adapters

1771ĆAS;

1771ĆASB (series A only);

1771ĆDCM

Miscellaneous

1771ĆAF

82W

32

16

connects to any device listed below:

Scanners

1771ĆSN; 1772ĆSD, ĆSD2;

1775ĆSR, ĆS4A, ĆS4B;

6008ĆSQH1, ĆSQH2

Adapters

1771ĆAS;

1771ĆASB (series A only);

1771ĆDCM

Miscellaneous

1771ĆAF

150W

16

16

operates at 57.6 or 115.2 K bit/s, and you do not

require over 16 physical devices

The scan list is a map of the I/O devices the scanner channel scans. To
create the scan list, use either of these commands:

If you want:

use this command:

the scanner to poll all available adapter addresses and assemble a

list with one entry for each adapter
in SVĆcompatible mode, there will be a maximum of 16 entries in

the scan list; in SVĆsuperset mode , there will be a maximum of 32

entries in the scan list

AUTOCONFIGURE

to create the scan list manually
add adapters multiple times in the scan list
there can be a maximum of 64 entries in the scan list, as long as

there are only 16 distinct physical adapters

SCAN LIST

Specifying a Scan List