Code

(hex):

Corrective Action:

Significance:

14

Block transfer queue full. The VME master processor

issued a block transfer command when the scanner's

block transfer queue was full.

Wait for one or more of the block transfers already in

the scanner's queue to finish, then reĆissue

the command.

15

Invalid length of data. The VME master processor

specified a length that cannot be used for the

command issued.

Specify a proper length.

16

Illegal configuration. The VME master processor

issued a:

SCAN LIST command that deletes an adapter listed

in a FAULT DEPENDENT GROUP.

command placing an adapter not in the scan list into

a FAULT DEPENDENT GROUP.

1. Adjust the fault dependent group and then reĆissue

the scan list.

2. Adjust the scan list and the reĆissue the fault

dependent group command.

23

Block transfer timeout. A block transfer specified by

the BT tag did not complete within 4 seconds and

was aborted.

1. Make sure a block transfer module is in the

slot specified.

2. Make sure the chassis holding the module is

turned on.

3. Make sure the adapter is in the scan list.

4. Make sure the scanner is not in the program mode.

5. Check the length of data value to make sure it

matches the module, or make the value zero.

6. Check the manual for the module in use.

25-2E

30-43

I/O link error. A failure occurred in the transfer of

information between the I/O module and the scanner.

An application program cannot cause these errors,

because they are associated with the communication

protocol on the I/O link.

1. Check the block transfer hardware configuration.

2. Eliminate electrical noise that may interfere with

remote I/O communication.

3. Use 57.6 kbps instead of 115.2 kpbs.

4. Ensure proper grounding of your I/O racks.

5. Consult the factory and/or replace the block

transfer module.

6. An error occurred within the scanner. Try cycling

power before removing the scanner.

2F

Block transfer accepted. The block transfer was

accepted by the scanner and is now in the

scanner's queue.

none