P.013 output relay configuration, P.012 terminal strip analog output source – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual
Page 107

4-21
Programming Reference
This parameter
specifies the type of
status indication
provided by the
output relay contacts
(terminal 28, 29, 30,
and 31 on the drive's
terminal strip).
Parameter Range:
0 = Output relay is energized when one or more
faults (IET) are active.
1 = Output relay is energized to show state of drive
running with 0.5 second delay added between a
start assertion and generation of motor voltage.
2 = Output relay is energized to show state of drive
running but without 0.5 second start delay.
3 = Output relay is energized when network
communication is active.
4 = Output relay is energized when all start
permissive conditions are met.
5 = Output relay is energized when one or more
alarms are active.
Default Setting:
0
Parameter Type:
Configurable
Refer also to parameters: N/A
P.012 Terminal Strip Analog Output Source
(continued)
Figure 4.2 – Analog Output Selection and Scaling
P.013 Output Relay Configuration
For example, for an application using an output contactor, you can obtain a 0.5
second delay between a start assertion and the generation of motor voltage by
setting P.013 to 1. The delay will provide time for the contactor to close before
motor voltage is generated.
10V
20 mA
0V
4 mA
0
0
10V
20 mA
0V
4 mA
– Max Speed
– Top Speed
–200% Torque
–300% Torque
+Max Speed (P.004)
+Top Speed (U.017)
+200% Torque
+300% Torque
P.012 = 0
P.012 = 1
V/Hz
Vector
V/Hz
Vector
V/Hz
Vector
V/Hz
Vector
– Max Speed
– Top Speed
–200% Max Current (2 x P.095)
–300% Torque
+Max Speed (P.004)
+Top Speed (U.017)
+200% Max Currenr (2 x P.095)
+300% Torque
P.012 = 2
P.012 = 3