4-91

Programming Reference

This parameter
specifies the amount
of control the outer
control loop output
signal has on the
speed loop
reference. It
represents a
percentage of Top
Speed (U.017).

Parameter Range:

0.0 to 100.0%

Default Setting:

0.0 (OCL output signal has no effect on speed loop

reference)

Parameter Type:

Tunable

Refer also to parameters: U.040 Outer Control Loop Feedback Source

U.041 Outer Control Loop Lead/Lag Select
U.042 Outer Control Loop Lead/Lag Low Frequency
U.043 Outer Control Loop Lead/Lag Ratio
U.044 Outer Control Loop Reference Gain
U.045 Outer Control Loop Proportional Gain
U.046 Outer Control Loop Integral Gain
U.048 Outer Control Loop Proportional Trim Enable

See Appendix G for the outer control loop block diagram.

This parameter
selects the integral
gain of the outer
control loop PI
amplifier.

Parameter Range:

0.01 to 141.37 radians/second

Default Setting:

2.00

Parameter Type:

Tunable

Refer also to parameters: U.040 Outer Control Loop Feedback Source

U.041 Outer Control Loop Lead/Lag Select
U.042 Outer Control Loop Lead/Lag Low Frequency
U.043 Outer Control Loop Lead/Lag Ratio
U.044 Outer Control Loop Reference Gain
U.045 Outer Control Loop Proportional Gain
U.047 Outer Control Loop Trim Range Percentage
U.048 Outer Control Loop Proportional Trim Enable

See Appendix G for the outer control loop block diagram.

U.046 Outer Control Loop Integral Gain

U.047 Outer Control Loop Trim Range Percentage