Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 211

Advertising
background image

F-3

Using the Terminal Strip Analog Input

Figure F.2 illustrates how the analog signal is scaled internally by the drive when it
is used as the speed or trim reference. The solid line indicates the conversion when
the non-inverted state is selected (P.011 is even). The dashed line indicates the
conversion when the inverted state is selected (P.011 is odd).

Figure F.2 – Analog Input Conversion Scaling (Speed or Trim Reference)

F.2.1 Adjusting for External Signal Errors Using the Offset and Gain

Parameters

When the analog input is used for speed or trim reference, parameters P.009
(Terminal Strip Analog Input Offset) and P.010 (Terminal Strip Analog Input Gain)
can be used to compensate for any offset or gain errors in the external circuitry.

The value in P.009 is first added to the converted 10-bit value and then the gain is
applied. If an offset or gain adjustment is needed, the offset should be adjusted
first, with the minimum input applied, and the gain adjusted last, with the maximum
input applied.

To remove a positive external offset, enter a negative value into P.009. In most
cases, the offset is left at the default value of zero and is only adjusted to counteract
external circuitry errors.

The adjustment range for P.009 is -900 to +900. For 0 to 10 V (or -10 V to +10 V)
input, a value of +1 equals an offset of approximately 10 mV. For 0 to 20 mA input,
a value of +1 equals an offset of approximately 20

µ

A.

+Max Spd

(P.004)

+Min Spd

(P.003)

-Min Spd

(P.003)

-10 vdc

+10 vdc

+20 ma

0 VDC
0 to 4 mA

-Max Spd

(P.004)

Terminal Strip Analog Input

P.011 is even = not inverted
P.011 is odd = inverted

Advertising