H.005 dc braking enable – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 146

Advertising
background image

4-60

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

H.004 = 100 x x = 5.56%

Synchronous RPM =

H.004 Slip Compensation

(continued)

120 x F
No. of Motor Poles

Example: 1722 RPM
Motor Nominal Current = 78% of Maximum Power Module Amps (P.095)
V/Hz regulation
2 kHz

1800 – 1722

100%

1800 78%

If the parameter is set to zero, motor speed will not be proportional to reference, but
will vary depending on load.

H.005 DC Braking Enable

This parameter
enables or disables
DC braking.

Parameter Range:

ON = Enable DC braking

OFF = Disable DC braking

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters: P.025 Stop Type

H.006 DC Braking Start Frequency
H.007 DC Braking Current
H.008 DC Braking Time
H.017 Input Power/Snubber Configuration

Important: This function will not provide holding torque as a mechanical brake. DC

braking is only operative when Stop Type (P.025) is set to 1 (ramp stop).

DC braking is used to provide additional motor braking (by DC current flow through
motor windings) at speeds below DC Braking Start Frequency (H.006). If DC braking is
required, DC braking functions (H.008, H.007) must be greater than zero (0).

When the motor decelerates to the preset DC Braking Start Frequency (H.006), the
DC Braking current (H.007) is applied to the motor after a Power Module-dependent
delay time.