H.000 Motor Nameplate Base Volts

This parameter
identifies the motor
nominal voltage as it
appears on the motor
nameplate.

Parameter Range:

100 VAC to 345 VAC

Default Setting:

230 VAC

Parameter Type:

Configurable

Refer also to parameters: N/A

H.001 Motor Nameplate Base Frequency

This parameter
configures the V/Hz
ratio.

Parameter Range:

30.0 Hz to 200.0 Hz

Default Setting:

60.0 Hz

Parameter Type:

Configurable

Refer also to parameters: H.003 Torque Boost Voltage

H.018 Volts/Hertz Curve Type

Base frequency is the frequency at which the output voltage reaches Motor
Nameplate Voltage (H.000). Below base frequency, the output voltage varies with
output frequency according to the V/Hz adjustment in parameter H.018 (Volts/Hertz
Curve Type). Above base frequency, output voltage is held constant as frequency
increases (constant horsepower range).

The V/Hz ratio is affected by the selection of Volts/Hertz Curve Type in H.018 and
the setting of Torque Boost Voltage in H.003. See figure 4.10.

Figure 4.10 – Volts/Hertz Ratio

100

30

H.001

Maximum

V/Hz

Minimum

V/Hz

Motor

Voltage,

(H.000)

(volts)

Output Frequency