4-38

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.045 Output Phase Loss Enable

This parameter is
used to enable the
output phase loss
detection diagnostic.

Parameter Range:

OFF = Disable output phase loss diagnostic

ON = Enable output phase loss diagnostic

Default Setting:

ON

Parameter Type:

Tunable

Refer also to parameters: N/A

This diagnostic detects phase loss between the drive and the motor. When the
diagnostic is enabled and output phase loss is detected, a drive fault is logged (OPL
is displayed).

The output phase loss diagnostic can be disabled to avoid nuisance faults which
may occur, for example, when a small motor is used with a large Power Module.

P.047 Carrier Frequency (kHz)

This parameter
selects the drive's
carrier frequency.

Parameter Range:

2 = 2 kHz Carrier frequency

4 = 4 kHz Carrier frequency

8 = 8 kHz Carrier frequency

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Configurable

Refer also to parameters: N/A

This parameter can compensate for acoustic noise by allowing adjustment of the
switching frequency of the transistors in the inverter bridge.

Keeping the carrier frequency at 8 kHz will ordinarily provide the quietest motor
operation.