P.060 network drop number, P.061 network connection type – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 133

Advertising
background image

4-47

Programming Reference

P.060 Network Drop Number

This parameter
specifies the base
drop number to
which the AutoMax
Network
Communication
Option Board will
respond on the
AutoMax network.

Parameter Range:

1 to 55 (Basic drive connection)

1 to 53 (Full drive connection)

Default Setting:

1

Parameter Type:

Configurable

Refer also to parameters: P.061 Network Connection Type

This parameter must be set at the drive via the keypad/display or via a personal
computer serial interface. This parameter cannot be written to the drive by the
network master.

For DeviceNet applications, refer to the DeviceNet Network Communication Option
Board manual (HE-HGV3DN).

For ControlNet applications, refer to the ControlNet Network Communication Option
Board manual (D2-3390).

P.061 Network Connection Type

This parameter
selects one of two
AutoMax network
connection types.

Parameter Range:

0 = Basic drive connection

1 = Full drive connection

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters: N/A

For DeviceNet applications, refer to the DeviceNet Network Communication Option
Board manual (HE-HGV3DN).

For ControlNet applications, refer to the ControlNet Network Communication Option
Board manual (D2-3390).

Setting P.061 = 0 provides basic drive control from the AutoMax network. Only
essential drive data (reference, sequencing, basic tuning, and feedback data) are
transferred over the network. This allows a higher density network with moderate
functionality. Select the basic connection type if your application does not require a
complete configuration of the drive over the network.

Using the basic drive connection, you can control functions such as start/stop, reset,
reference, and basic tunable parameters such as accel, decel, minimum speed,
maximum speed, etc. See instruction manual D2-3308 (AutoMax Network
Communications Option Board) for a complete list of parameters that can be
controlled.

When basic drive connection is selected, the GV3000/SE drive occupies a single
network drop. This drop area contains 32 read registers and 32 write registers.

Advertising