2-29

Starting Up the Drive for Vector Regulation

Step 8.4 Press the ENTER key.

After pressing ENTER, the same parameter
is displayed. You can now go to the next
step.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 8.5 Press the PROGRAM key twice to exit program mode.

This display flashes S-En. This reminds you
that the self-tuning procedure is enabled.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 8.6 Press the START key to begin the self-tuning procedure.

ATTENTION: The motor will rotate during the self-tuning procedure.
Stay clear of rotating machinery. Failure to observe this precaution
could result in severe bodily injury or loss of life.

The display flashes S-Ac, indicating that the
self-tuning procedure is active.

This procedure takes a few minutes. S-Ac
flashes on the display until the procedure is
complete.

The motor should be rotating in the
counter-clockwise (CCW) direction when
viewed from the driven motor shaft end.

!

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

CCW