Programming Reference

P.022 Jog Ramp Decel Time

For V/Hz regulation,
this parameter
specifies the amount
of time it takes the
motor to ramp from
Maximum Speed
(P.004) to zero
speed when JOG is
selected.

For vector regulation,
this parameter
specifies the amount
of time it takes the
motor to ramp from
Motor Top Speed
(U.017) to zero
speed when JOG is
selected.

The time the motor takes to make any speed decrease (except a coast-to-rest stop)
is directly proportional to the value in this parameter.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)
0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters: P.004 Maximum Speed

P.025 Stop Type
U.017 Motor Top Speed

P.023 MOP Accel/Decel Time

Parameter Range:

0.1 to 999.9 seconds

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters: P.004 Maximum Speed

P.007 Terminal Strip Digital Inputs Configure
P.008 Terminal Strip Speed Reference Source
U.017 Motor Top Speed

The MOP (Motor Operated Potentiometer) is a digital reference controlled by the
increment/decrement inputs.

For V/Hz regulation,
this parameter
specifies the amount
of time it takes the
MOP to ramp from
Maximum Speed
(P.004) to zero
speed and from zero
speed to Maximum
Speed (P.004).

For vector regulation,
this parameter
specifies the amount
of time it takes the
MOP to ramp from
Motor Top Speed
(U.017) to zero
speed and from zero
speed to Motor Top
Speed (U.017).