ATTENTION: The subsequent steps require rotating parts and/or
electrical circuits to be exposed. Stay clear if unit must be running, or
disconnect and lock out or tag power source if contact must be made.
Failure to observe this precaution could result in severe bodily injury or
loss of life.

Important: The stop input on the terminal strip is not active when the Control

Source parameter (P.000) is set to LOCL, as it is during this start-up
procedure. Use the STOP/RESET key if you need to stop the drive.

Step 7. Check Motor Rotation Direction

This step involves verifying the speed reference is set to minimum speed, starting
the drive, and checking that the motor rotates in the correct direction. It is
performed with the motor disconnected from the load.

!

Step 7.1 Press the PROGRAM key until the PROGRAM LED turns off.

The keypad/display will enter monitor mode.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 7.2 Verify that the AUTO LED is off (press the AUTO/MAN key until the

AUTO LED turns off).

This selects the local keypad as the speed
reference source.

Step 7.3 Press the

£

key or the

¥

key once.

The monitor mode LEDs will all turn off and
the manual speed reference value will be
displayed. The speed reference value is in
the units defined in P.028. The display
shown here is only an example.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 7.4 If the speed reference is at minimum speed, then proceed to Step 7.6.

If the speed reference is not at minimum speed, proceed to Step 7.5.