Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual
Page 22

1-8
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 3.15 Press the ENTER key to display the default setting of P.004.
ATTENTION: The user is responsible for ensuring that driven machinery,
all drive-train mechanisms, and application material are capable of
safe operation at the maximum operating speed of the drive. In V/Hz
regulation, overfrequency protection in the drive is provided by means
of H.022. Failure to observe this precaution could result in bodily
injury.
!
This shows that the default setting for
Maximum Speed is 60.0 Hz.
Step 3.16 Press the
£
key to increase maximum speed or the
¥
key to decrease
maximum speed.
The adjustment range is:
15.0 Hz to the value set for H.022
(Overfrequency Limit).
The maximum value is 210 Hz.
VALUE ENTERED:
Step 3.17 Press the ENTER key to save the changed value.