Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 69

Advertising
background image

2-31

Starting Up the Drive for Vector Regulation

Step 9.3 Press the

£

key until U.009 is displayed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 9.4 Press the ENTER key to view the test result.

Step 9.5 Refer to the U.009 parameter description in chapter 4 for the

corresponding cause and corrective action.

Step 9.6 Once the cause of the fault has been corrected, repeat the self-tuning

procedure (Step 8).

ATTENTION: The subsequent steps require rotating parts and/or
electrical circuits to be exposed. Stay clear if the drive must be running, or
disconnect and lock out or tag power source if contact must be made.
Failure to observe this precaution could result in severe bodily injury or
loss of life.

Important: The stop input on the terminal strip is not active when the Control

Source parameter (P.000) is set to LOCL, as it is during this start-up
procedure. Use the STOP/RESET key if you need to stop the drive.

Step 10. Check Motor Rotation Direction

This step involves verifying the speed reference is set to minimum speed, starting
the drive, and checking that the motor rotates in the correct direction. It is
performed with the motor disconnected from the load.

!

Step 10.1 Press the PROGRAM key until the PROGRAM LED turns off.

The keypad/display will enter monitor mode.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM