Starting Up the Drive for Vector Regulation

The adjustment range is:

10 to Motor Top Speed (set in parameter
U.017). Refer to Step 7 for parameter
U.017.

VALUE ENTERED:

Step 5.17 Press the

£

key to increase maximum speed or the

¥

key to decrease

maximum speed.

Step 5.18 Press the ENTER key to save the changed value.

After pressing ENTER, the same parameter
number is displayed. You can now go to the
next step.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 5.19 Press the

£

key until P.005, Current Limit, is displayed.

This parameter sets the stator current limit
as a percentage of motor rated amps.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 5.20 Press the ENTER key to display the default setting of P.005.

This display is the default setting for Current
Limit, 150% of the value entered in U.004.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM