4-22

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

Figure 4.3 – Trim Reference Source Selection

P.014 Trim Reference Source

This parameter
specifies the source
for the trim
reference. Trim
reference is added to
the speed reference.

Refer to figure 4.3.

Parameter Range:

0 = No trim reference used

1 = Terminal strip analog input

2 = Option port trim reference register

3 = Maximum speed

4 = Torque current feedback (vector only)

5 = RMI board analog input

6 = RMI board frequency input

7 = Switched RMI board analog input or frequency

input

8 = RMI outer loop PI block (Mode 1)

9 = RMI outer loop PI block (Mode 2)

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters: P.015 Trim Gain Percentage

Selections 5 through 9 are available only if an optional RMI board is installed in the
drive. Refer to instruction manual D2-3341 for more information about the RMI
board.