P.014 Trim Reference Source
This parameter
specifies the source
for the trim
reference. Trim
reference is added to
the speed reference.
Refer to figure 4.3.
Parameter Range:
0 = No trim reference used
1 = Terminal strip analog input
2 = Option port trim reference register
3 = Maximum speed
4 = Torque current feedback (vector only)
5 = RMI board analog input
6 = RMI board frequency input
7 = Switched RMI board analog input or frequency
input
8 = RMI outer loop PI block (Mode 1)
9 = RMI outer loop PI block (Mode 2)
Default Setting:
0
Parameter Type:
Configurable
Refer also to parameters: P.015 Trim Gain Percentage
Selections 5 through 9 are available only if an optional RMI board is installed in the
drive. Refer to instruction manual D2-3341 for more information about the RMI
board.