H.019 identification result, H.018 volts/hertz curve type – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 153

Advertising
background image

4-67

Programming Reference

Figure 4.13 – Volts/Hertz Curve Selection

H.018 Volts/Hertz Curve Type

(continued)

H.019 Identification Result

This parameter
displays the result of
the identification
procedure. Normally,
the identification
procedure will be
successful, and the
value in H.019 will be
= 0.

Parameter Range:

0 = Identification procedure successful. No fault.

1 = A logged error aborted the identification

procedure. Refer to section 5.3 for how to
determine the cause of the fault. Remove the
cause and repeat the procedure.

2 = A function loss aborted the identification

procedure. Depending on Function Loss
Response (P.026), this is or is not logged.
Remove the cause and repeat the procedure.

3 = A stop command aborted the identification

procedure. Repeat the procedure without
stopping.

4 = The identification procedure aborted because the

measured current feedback signal is too low.
Feedback signal elements or wiring is defective.
Check motor connections, inverter wiring, and
feedback devices (current sensors). Repeat
procedure.

6 = Calculation result based on identification

procedure measurements is out of range. Check
causes of incorrect measurements, such as
motor connections. Repeat procedure.

Default Setting:

0

Parameter Type:

Read only

Refer also to parameters: H.020 Identification Request

Motor

Base Frequency

(H.001)

Hz

Motor

Voltage
(H.000)

Motor

Voltage
(H.000)

Motor

Voltage
(H.000)

Motor

Base Frequency

(H.001)

Volts

Volts

Volts

Hz

Motor

Base Frequency

(H.001)

Hz

Linear (0)

Optimized (1)

Squared (2)