4-32

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.029 Elapsed Time Meter

This parameter
displays the number
of days (24-hour
periods) that the
drive has been under
power or the time
elapsed since the
Elapsed Time Meter
Reset (P.030)
parameter was last
reset.

Parameter Range:

0 to 9999 days

Default Setting:

N/A

Parameter Type:

Read only

Refer also to parameters: P.030 Elapsed Time Meter Reset

P.030 Elapsed Time Meter Reset

Parameter Range:

OFF = No action

ON = Reset the Elapsed Time Meter (P.029) and

the error log clock to zero (0).

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters: P.029 Elapsed Time Meter

P.031 to P.038 Preset Speed 1 Through Preset Speed 8

This parameter
allows the setting of
up to eight different
preset speeds.

The presets are configured using parameters P.007 and P.008. P.008 must be set
to values of 2 through 7 for preset speeds. See table 4.4 and figure 4.6.

Parameter Range:

Minimum Speed (P.003) to Maximum Speed (P.004)

Default Setting:

5.0 Hz (V/Hz)
150 RPM (vector)

Parameter Type:

Tunable

Refer also to parameters: P.007 Terminal Strip Digital Inputs Configure

P.008 Terminal Strip Speed Reference Source

This parameter sets
parameter P.029
(Elapsed Time
Meter) and the error
log clock to zero.
This parameter is set
to OFF after the
reset operation is
carried out.