E-1

Configuring the Digital Inputs When the RMI Board Is Installed in the Drive

A

PPENDIX

E

Configuring the Digital Inputs

When the RMI Board Is

Installed in the Drive

The GV3000/SE Regulator board contains three user-configurable digital inputs.
Parameter P.007 (Terminal Strip Digital Inputs Configure) and P.008 (Terminal Strip
Speed Reference Source) are used to specify how these digital inputs are used.

If an optional Remote Meter Interface (RMI) board is installed in the drive, four
additional digital inputs are available. RMI parameter r.030 is used to specify how
the RMI digital inputs are used.

The Regulator board digital inputs and the RMI digital inputs are not permitted to be
used for the same functions. One parameter cannot be set to a value which requires
resources (digital inputs) or a duplication of function which is used or defined by the
value of another parameter.

The acceptable values for P.008 are based on the value selected for P.007 and by
the value selected for r.030:

P.008 is limited by P.007 and r.030

P.007 is limited by P.008

r.030 is limited by P.008

First determine what functions are to be assigned to the three digital inputs on the
Regulator board. Once you have determined this, select the appropriate settings for
P.007 and P.008. As shown in the following tables, the desired value for P.008
must be permissible by both the P.007 and r.030 values.
If either column
indicates the value is not acceptable, then P.008 cannot be set to that value. Use
the following tables to help determine the appropriate settings for your application.

Refer to chapter 4 in this manual for a complete description of parameters P.007
and P.008 and their corresponding options. Refer to the RMI board instruction
manual (D2-3341) for a complete description of parameter r.030 and its options.