Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 110

Advertising
background image

4-24

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.017 Accel Time 2 (RAMP 2)

This parameter sets
the acceleration time
when a second ramp
selection is
configured as a
digital input.

When the RAMP 2
acceleration time
digital input is
asserted, the RAMP
2 deceleration time
also takes effect.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)
0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters: P.001 Accel Time 1

P.007 Terminal Strip Digital Inputs Configure

In V/Hz regulation, this parameter specifies the time in which the motor ramps from
zero speed to Maximum Speed (P.004).

In vector regulation, this parameter specifies the time in which the motor ramps from
zero speed to Motor Top Speed (U.017).

The time it takes the motor to make any speed increase is directly proportional to
the value in this parameter. This parameter does not apply if JOG is selected.

P.018 Decel Time 2 (RAMP 2)

This parameter
specifies the
deceleration time
when a second ramp
selection is
configured as a
digital input.

When the RAMP 2
deceleration time
digital input is
asserted, the RAMP
2 acceleration time
also takes effect.

In V/Hz regulation, this parameter specifies the time in which motor speed ramps
from Maximum Speed (P.004) to zero speed.

In vector regulation, this parameter specifies the time in which motor speed ramps
from Motor Top Speed (U.017) to zero speed.

The time it takes the motor to make any speed decrease (except a coast-to-rest
stop) is directly proportional to the value in this parameter.

This parameter does not apply if JOG is selected.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)
0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters: P.002 Decel Time 1

P.007 Terminal Strip Digital Inputs Configure

Advertising