4 ensuring program security – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 91

Advertising
background image

4-5

Programming Reference

Step 7. Press the ENTER key to save the changed value.

- OR -
Press the PROGRAM key to exit the parameter without changing the
value.

The parameter number will be displayed
again.

Important: The value will not be written into

memory unless the ENTER key
is pressed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

To display or change additional parameters within this menu, repeat step 4
through 7.

To display or change parameters in a different menu, press the PROGRAM key
to return to the main menu selections. Then repeat step 2 through 7.

To exit program mode, press the PROGRAM key until the PROGRAM LED turns off.

Note that parameter values and the local keypad status are retained through a line
dip or power shutdown.

4.4

Ensuring Program Security

Parameter values can be password-protected using parameter P.051 (Programming
Disable). When programming is disabled, parameter values can be displayed but
cannot be modified from the keypad unless the correct password is entered in
P.051. Note that disabling program changes by means of P.051 will not prevent
parameter changes being made from the serial port on the network.

ATTENTION: It is the user's responsibility to determine how to distribute
the password. Reliance Electric is not responsible for unauthorized
access violations within the user's organization. Failure to observe this
precaution could result in bodily injury.

Use the following procedure to disable/enable parameter programming. (See
section 4.3, Displaying or Changing Parameter Values, if you are unfamiliar with
modifying parameters using the keypad/display.)

Step 1. Select parameter P.051 from the Second Menu General parameters.

P.051 will appear on the display.

Step 2. Press the ENTER key to access the parameter. A zero will be displayed.

Step 3. Use the

£

key to increment the value to 26. This is the password number.

Step 4. Press the ENTER key to save the value. P.051 will be displayed.

Parameter programming is disabled when the PASSWORD LED is on and enabled
when the PASSWORD LED is off.

!