P.050 restore defaults, P.051 programming disable – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 126

Advertising
background image

4-40

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.050 Restore Defaults

This parameter
resets all First and
Second Menu
General parameters
(P.---) to factory
default settings.

Parameter Range:

OFF = No action

ON = Reset parameters to default settings

Default Setting:

OFF

Parameter Type:

Configurable

Refer also to parameters: P.049 Country Defaults

Note that P.048 (Volts/Hertz or Vector Regulation) is not restored to its factory
default setting when P.050 is set to ON.

P.051 Programming Disable

When the password
is entered into this
parameter,
parameter values
cannot be modified
from the keypad
unless the correct
password is entered
again. Refer to
section 4.4, Ensuring
Program Security, for
more information.

Parameter Range:

0 to 9999

Default Setting:

0 (Programming enabled)

Parameter Type:

Tunable

Refer also to parameters: N/A

ATTENTION: It is user's responsibility to determine how to distribute
the password. Reliance Electric is not responsible for unauthorized
access violations within the user's organization. Failure to observe this
precaution could result in bodily injury.

The PASSWORD LED will be on to indicate parameters cannot be modified from
the keypad.

Note that disabling program changes by means of P.051 will not prevent parameter
changes being made from the serial port on the network.

!

Advertising