P.065 option port: type and version, P.064 option port: network trim reference source – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 138

Advertising
background image

4-52

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

This parameter
specifies where the
drive gets its trim
reference when the
option port is
selected as the
control source
(P.000 = OP).

Parameter Range:

0 = Direct trim reference register

1 to 8 = Broadcast register 1 to 8, respectively

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters: P.063 Option Port: Network Reference Source

U.000 Torque Reference Source

This parameter
displays the option
type and the software
version number of
the option board.

P.065 Option Port: Type and Version

The display format is N.vvv, where N represents the option type (1 = RMI,
2 = AutoMax network or PROFIBUS network, 4 = DeviceNet network, and 5 =
ControlNet network) and v represents the software version number.

For example, if 2.103 is displayed, it means the drive is using the AutoMax network
option and is running version 1.03 software.

Parameter Range:

N/A

Default Setting:

N/A

Parameter Type:

Read only

Refer also to parameters: N/A

P.064 Option Port: Network Trim Reference Source

The option port trim reference is used as the outer control loop reference and/or the
speed trim reference (see the P.014 (Trim Reference Source) parameter
description).

If P.064 = 0, the trim reference is from register 34 of the first drop image.

If P.064 = 1 to 8, the trim reference is from network broadcast registers 1 through 8,
respectively. For a description of the broadcast registers, refer to the AutoMax
Network Communication Module manual (J2-3001).

In V/Hz regulation, the trim reference represents speed in hertz scaled 0 to 4095 for
0 to Maximum Speed (P.004).

In vector regulation, the trim reference represents speed scaled 0 to 4095 for 0 to
Top Speed (U.017). When used for the outer control loop, the value should be
scaled based on the scaling of the selected feedback.

Refer to Appendix G for more information.