Step 12. Tune the Speed Regulator

Tuning the speed regulator consists of adjusting the speed regulator proportional
and integral gain values according to the application. The speed regulator uses
these values to calculate the drive's response to a change in speed reference and to
changes in load or other factors in the driven system. This procedure may or may
not be required. This step assumes you have connected the motor to the load.

Step 12.1 Press the START key.

The drive is now running. The
keypad/display is in monitor mode, and the
RUNNING and FORWARD LEDs are on.
Speed is displayed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Sep 12.2 Press the PROGRAM key to enter program mode.

The PROGRAM LED is on and the First
Menu General (P) parameter main menu is
displayed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 12.3 Press the

£

key until U.– – – is displayed.

The error log (Err) is bypassed, then the
Vector (U) parameter main menu is
displayed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM