P.052 auto/man key disable – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 127

Advertising
background image

4-41

Programming Reference

Parameter Range:

OFF = Enable the AUTO/MAN key regardless of

control source

ON = Disable the AUTO/MAN key except from the

selected control source

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters: P.000 Control Source

P.053 Manual Reference Preset Enable

P.052 AUTO/MAN Key Disable

This parameter
disables the
AUTO/MAN key
except from the
selected control
source.

When this parameter is set to ON, the AUTO/MAN key is functional only from the
selected control source. This parameter can be used to protect against inadvertent
reference change when the drive is controlled from the terminal strip (P.000 = rE) or
the option port (P.000 = OP).

Table 4.6 details whether the AUTO/MAN key is active based on the selected
control source and P.052.

Table 4.6 – AUTO/MAN Key Status Based on P.000 and P.052

Control Source (P.000 =)

Front panel (LOCL)

Terminal strip (rE)

Network/option board (OP)

OIM/CS3000 (SErL)

Front panel (LOCL)

Terminal strip (rE)

Network/option board (OP)

OIM/CS3000 (SErL)

P.052

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Front Panel

AUTO/MAN Key

Active

Active

Active

Inactive

Active

Inactive

Inactive

Inactive

OIM/CS3000

AUTO/MAN Key

Inactive

Active

Active

Active

Inactive

Inactive

Inactive

Active